MPL INDIA HEAT SHRINKABLE TERMINATIONS UPTO 36 kV For PILC Cable
In conformance with IEEE-48,
VDE 0278 & IS: 13573.
Test Item of Heat Shrinkable Termination as per IEC-60502-4 / IS:13573
Testing Items U o/U | 6.35/11 kV | 12.7/22 kV | 19/33 kV |
---|---|---|---|
A.C. withstand test | 29kV, 5min, no flashover | 58kV, 5min, no flashover | 86kV, 5min, no flashover |
Partial discharge test | 11kV < 10pc (Max.) | 22kV < 10pc (Max.) | 33kV < 10pc (Max.) |
Thermal Cycles (63 cycles) | under 95-100o C 16kV | under 95-100o C 32kV | under 95-100o C 48kV |
Impulse voltage test | 75kV no flashover | 125kV no flashover | 170kV no flashover |
A.C. with stand test | 16kV, 15 min, no flashover | 32kV, 15 min, no flashover | 48kV, 15 min, no flashover |
Humidity test (Indoor) | No flashover, tracking erosion or mechanical damage occured at 300hrs, 8kV | No flashover, tracking erosion or mechanical damage occured at 300hrs, 16kV | No flashover, tracking erosion or mechanical damage occured at 300hrs, 24kV |
Salt Fog test (Outdoor) | No flashover, tracking erosion or mechanical damage occured at 1000hrs, 8kV no flashover, tracking | No flashover, tracking erosion or mechanical damage occured at 1000hrs, 16kV no flashover, tracking | No flashover, tracking erosion or mechanical damage occured at 1000hrs, 24kV no flashover, tracking |
CABLE SIZE (Sq. mm) | 11 kV, 3 core Indoor Terminations | |
---|---|---|
3 x 16 - 50 | MXSE - 11 | Enquire now |
3 x 70 - 95 | MXSE - 12 | Enquire now |
3 x 120 - 185 | MXSE - 13 | Enquire now |
3 x 240 - 300 | MXSE - 14 | Enquire now |
3 x 400 - 500 | MXSE - 15 | Enquire now |
CABLE SIZE (Sq. mm) | 11 kV , 3 core Outdoor Terminations | |
---|---|---|
3 x 16 - 50 | MXSO - 11 | Enquire now |
3 x 70 - 95 | MXSO - 12 | Enquire now |
3 x 120 - 185 | MXSO - 13 | Enquire now |
3 x 240 - 300 | MXSO - 14 | Enquire now |
3 x 400 - 500 | MXSO - 15 | Enquire now |
CABLE SIZE (Sq. mm) | 22 kV, 3 core Indoor Terminations | |
---|---|---|
3 x 16 - 50 | MXSE - 21 | Enquire now |
3 x 70 - 120 | MXSE - 22 | Enquire now |
3 x 150 - 225 | MXSE - 23 | Enquire now |
3 x 240 - 400 | MXSE - 24 | Enquire now |
3 x 500 | MXSE - 25 | Enquire now |
CABLE SIZE (Sq. mm) | 22 kV, 3 core Outdoor Terminations | |
---|---|---|
3 x 16 - 50 | MXSO - 21 | Enquire now |
3 x 70 - 120 | MXSO - 22 | Enquire now |
3 x 150 - 225 | MXSO - 23 | Enquire now |
3 x 240 - 400 | MXSO - 24 | Enquire now |
3 x 500 | MXSO - 25 | Enquire now |
CABLE SIZE (Sq. mm) | 33 kV, 3 core Indoor Terminations | |
---|---|---|
3 x 25 - 50 | MXSE - 31 | Enquire now |
3 x 70 - 95 | MXSE - 32 | Enquire now |
3 x 120 - 185 | MXSE - 33 | Enquire now |
3 x 240 - 400 | MXSE - 34 | Enquire now |
CABLE SIZE (Sq. mm) | 33 kV, 3 core Outdoor Terminations | |
---|---|---|
3 x 25 - 50 | MXSO - 31 | Enquire now |
3 x 70 - 95 | MXSO - 32 | Enquire now |
3 x 120 - 185 | MXSO - 33 | Enquire now |
3 x 240 - 400 | MXSO - 34 | Enquire now |