DENSONS HEAT SHRINKABLE TERMINATIONS UPTO 15 kV For Single Core XLPE/EPR Insulated Cable
In conformance with IEEE-48,
VDE 0278 & IS: 13573.
Type Test Reports Available On Request
TEST | TYPE XSO/ES - 1115 |
---|---|
A.C. Dry withstand Voltage | 35 kV / I min. |
Impulse withstand Voltage | 75 kV, 10+ve Shots |
Corona extinction Voltage | More than 13 kV |
CABLE SIZE (Sq. mm) | INDOOR (Kit Code) | |
---|---|---|
1 x 16 - 50 | XSES - 11 | Enquire Now |
1 x 70 - 120 | XSES - 12 | Enquire Now |
1 x 150 - 300 | XSES - 13 | Enquire Now |
1 x 400 - 630 | XSES - 14 | Enquire Now |
1 x 800 - 1000 | XSES - 15 | Enquire Now |
CABLE SIZE (Sq. mm) | OUTDOOR (Kit Code) | |
1 x 25 - 50 | XSOS - 11 | Enquire Now |
1 x 70 - 120 | XSOS - 12 | Enquire Now |
1 x 150 - 300 | XSOS - 13 | Enquire Now |
1 x 400 - 630 | XSOS - 14 | Enquire Now |
1 x 800 - 1000 | XSOS - 15 | Enquire Now |