Property | Requirements | Test Method |
---|---|---|
Physical | ||
Specific gravity | 1.19 | ASTM D 1505 / ISO 1183 |
Tensile Strength | 8 N/mm2 (min.) | ASTM D 412 / ISO 37 |
Ultimate elongation | 200% (min) | ASTM D 412 / ISO 37 |
Water absorption | 0.5% (max.) | ASTM D 570 |
Thermal Ageing Continuous operating temperature |
-55oC to + 130o C | IEC 216 |
Shrink temperature | 120o C (min.) | IEC 216 |
Heat shock (30 min. 200 C) | No cracking / No flowing | |
Heat ageing (168 hrs. 120 C) | ||
Tensile strength | 7.0 N/mm2 (min.) | ASTM D 412 / ISO 37 |
Ultimate elongation | 200% (min.) | |
Low temperature flexibility (-20 C) | No cracking | ASTM D 2671 |
Flammability | Self extinguishing | ASTM D 2671 - B |
Electrical | ||
Dielectric Strength | 10 kV/mm (min.) | ASTM D149, IEC 243 |
Volume Resistivity | 1 x 1012 ohm-cm (min.) | ASTM D 257 / IEC 93 |
Dielectric constant | 3 (min.) to 5 (max.) | ASTM D 150 / IEC 250 |
Tracking erosion resistance | No tracking or erosion up to 3.25 kV | ASTM D 2303 |
Code | Expanded D1 | Recovered D2 | W (Recovered) | |
---|---|---|---|---|
MSRU 36/12 | 36 | 12 | 2.8 | Enquire Now |
MSRU 42/19 | 42 | 19 | 2.9 | Enquire Now |
MSRU 60/29 | 60 | 29 | 3.0 | Enquire Now |
MSRU 76/38 | 76 | 38 | 3.0 | Enquire Now |
MSRU 100/49 | 100 | 49 | 3.0 | Enquire Now |
MSRU 130/50 | 130 | 50 | 4.0 | Enquire Now |